2.2.244. SPN 4376, FMI 5, DEF pump direction valve: Low side current below normal or open circuitΒΆ
Description
The measured DEF pump direction valve low side current is below normal or open circuit.
Possible causes are:
- The DEF supply module direction valve wiring is defective. (Shorted to low side or open circuit.)
- The DEF supply module is defective.
Reaction in EEM
The FC is stored and the warning lamp is activated. The CAN message indicates an active fault.
NOTE: The present fault is classified as an emission related fault. Engine power is reduced after a certain time defined by an authority.
Solution
First save the error log and then do the procedure that follows:
- Examine the DEF supply module direction valve wiring, the connectors and the contact surfaces of the connector pins (possible oxidation).
- Test the operation with another DEF supply module to see if the supply module is defective.
See Supply module sensor for reference.